Fixing wrong range validations
This commit is contained in:
@@ -186,7 +186,7 @@ namespace AMWD.Protocols.Modbus.Serial
|
||||
|
||||
private Task StopAsyncInternal(CancellationToken cancellationToken)
|
||||
{
|
||||
_stopCts.Cancel();
|
||||
_stopCts?.Cancel();
|
||||
|
||||
_serialPort.Close();
|
||||
_serialPort.DataReceived -= OnDataReceived;
|
||||
@@ -328,7 +328,7 @@ namespace AMWD.Protocols.Modbus.Serial
|
||||
ushort firstAddress = requestBytes.GetBigEndianUInt16(2);
|
||||
ushort count = requestBytes.GetBigEndianUInt16(4);
|
||||
|
||||
if (TcpProtocol.MIN_READ_COUNT < count || count < TcpProtocol.MAX_DISCRETE_READ_COUNT)
|
||||
if (count < RtuProtocol.MIN_READ_COUNT || RtuProtocol.MAX_DISCRETE_READ_COUNT < count)
|
||||
{
|
||||
responseBytes[1] |= 0x80;
|
||||
responseBytes.Add((byte)ModbusErrorCode.IllegalDataValue);
|
||||
@@ -385,7 +385,7 @@ namespace AMWD.Protocols.Modbus.Serial
|
||||
ushort firstAddress = requestBytes.GetBigEndianUInt16(2);
|
||||
ushort count = requestBytes.GetBigEndianUInt16(4);
|
||||
|
||||
if (TcpProtocol.MIN_READ_COUNT < count || count < TcpProtocol.MAX_DISCRETE_READ_COUNT)
|
||||
if (count < RtuProtocol.MIN_READ_COUNT || RtuProtocol.MAX_DISCRETE_READ_COUNT < count)
|
||||
{
|
||||
responseBytes[1] |= 0x80;
|
||||
responseBytes.Add((byte)ModbusErrorCode.IllegalDataValue);
|
||||
@@ -442,7 +442,7 @@ namespace AMWD.Protocols.Modbus.Serial
|
||||
ushort firstAddress = requestBytes.GetBigEndianUInt16(2);
|
||||
ushort count = requestBytes.GetBigEndianUInt16(4);
|
||||
|
||||
if (TcpProtocol.MIN_READ_COUNT < count || count < TcpProtocol.MAX_REGISTER_READ_COUNT)
|
||||
if (count < RtuProtocol.MIN_READ_COUNT || RtuProtocol.MAX_REGISTER_READ_COUNT < count)
|
||||
{
|
||||
responseBytes[1] |= 0x80;
|
||||
responseBytes.Add((byte)ModbusErrorCode.IllegalDataValue);
|
||||
@@ -496,7 +496,7 @@ namespace AMWD.Protocols.Modbus.Serial
|
||||
ushort firstAddress = requestBytes.GetBigEndianUInt16(2);
|
||||
ushort count = requestBytes.GetBigEndianUInt16(4);
|
||||
|
||||
if (TcpProtocol.MIN_READ_COUNT < count || count < TcpProtocol.MAX_REGISTER_READ_COUNT)
|
||||
if (count < RtuProtocol.MIN_READ_COUNT || RtuProtocol.MAX_REGISTER_READ_COUNT < count)
|
||||
{
|
||||
responseBytes[1] |= 0x80;
|
||||
responseBytes.Add((byte)ModbusErrorCode.IllegalDataValue);
|
||||
|
||||
Reference in New Issue